Acuvim-l Series Multifunction Power Meter





Inquiry Catalog

Description

  • Power Meter Measures 3-Phase Voltage, Current, Power (Reactive, Apparent, Active), Energy, Power Factor, Run Time, THD and Individual Harmonics to 15th and 25th order
  • (6) Different Model Options Provide for Digital Output, RS-485 Communications and Time-of-Use
  • (2) Different Alarm Parameters for High and Low Alarm Alerts
  • Compatible with Single or Three-Phase Electrical Systems
  • (2) Pulse Digital Outputs for kWh and kvarh with Configurable Rate and Width
  • ±0.2% Accuracy with ANSI C12.20 Standard for Revenue Grade Meters

Feature

 

Includes AcuView Software


Spesification

VoltageRange: 20 Volts to 500 kiloVolts
Accuracy: 0.5%
Resolution: 0.1 VoltsCurrentRange: 0 to 50,000 Amps
Accuracy: 0.5%
Resolution: 0.001 AmpsCurrent DemandRange: 0 to 50,000 Amps
Accuracy: 0.5%
Resolution: 0.001 AmpsPowerRange: -9999 MW to 9999 MW
Accuracy: 1.0% (0.5% - EL and KL Versions)
Resolution: 1 WattReactive Power Range: -9999 MVar to 9999 MVar
Accuracy: 1.0% (0.5% - EL and KL Versions)
Resolution: 1 VarApparent Power Range: 0 to 9999 MVA
Accuracy: 1.0% (0.5% - EL and KL Versions)
Resolution: 1 VAPower Demand Range: -9999 MW to 9999 MW
Accuracy: 1.0% (0.5% - EL and KL Versions)
Resolution: 1 WReactive Power Demand Range: -9999MVar to 9999MVar
Accuracy: 1.0% (0.5% - EL and KL Versions)
Resolution: 1 VarApparent Power Demand Range: 0 to 9999 MVA
Accuracy: 1.0% (0.5% - EL and KL Versions)
Resolution: 1 VAPower FactorRange: -1.0 to 1.0
Accuracy: 1.0% (0.5% - EL and KL Versions)
Resolution: 0.001FrequencyRange: 45.00 Hz to 65.00 Hz
Accuracy: 1.0% (0.2% - EL and KL Versions)
Resolution: 0.01 HzEnergyRange: 0 to 99,999,999.9 kWh
Accuracy: 0.5%
Resolution: 0.1 kWhReactive EnergyRange: 0 to 99,999,999.9 kVarh
Accuracy: 1.0% (0.5% - EL and KL Versions)
Resolution: 0.1 kvarhApparent EnergyRange: 0 to 99,999,999.9 kVAh
Accuracy: 1.0% (0.5% - EL and KL Versions)
Resolution: 0.1 VAhHarmonicsRange: 0 to 100%
Accuracy: 2.0%
Resolution: 0.1%Running Time Range: 0 to 9,999,999.99 hours
Resolution: 0.1 hoursCurrent Inputs
(Each Channel)
Nominal Current: 5A ac
Metering Range: 0 to 6 A ac
Withstand: 20 Arms (Continuous); 100 Arms (1 Sec., non-recurring)
Burden: 0.05VA (typical) @ 5Arms
Pickup Current: 0.1% of Nominal
Accuracy: 0.5%Voltage Inputs
(Each Channel)
Nominal Full Scale: 400 Vac L-N, 690 Vac L-L
Withstand: 1500Vac (Continuous); 2500 Vac, 50/60 Hz (1 min.)
Input Impedance: 2Mohm per phase
Metering Frequency: 45 Hz to 65 Hz
Pickup Voltage: 10Vac
Accuracy: 0.5%Energy Accuracy Active: Class 0.5S (According to IEC 62053-22)
Reactive: Class 2 (According to IEC 62053-23)Harmonic Resolution Metered Value: 2nd to 15th Harmonic (2nd to 25th Harmonic - DL Version)AC/DC Control PowerOperating Range: 100-415 Vac; 100-300 Vdc
Burden: 5W
Frequency: 50/60 Hz
Withstand: 3250 Vac, 50/60 Hz for 1 Minute
Installation Category III (Distribution)Low Voltage DC Control Power (Optional) Operating Range: 20 to 60 Vdc
Burden: 5WDigital Input (DI) Input Voltage Range: 20 to 220 Vac/dc
Input Current (Max): 2mA
Start Voltage: 15 Volts
Stop Voltage: 5 Volts
Pulse Frequency (Max): 100 Hz, 50% Duty Ratio (5ms ON and 5ms OFF)
SOE Resolution: 2 msDigital Output (DO)
(Photo-MOS)
Voltage Range: 0 to 250 Vac/dc
Load Current: 100mA (Max)
Output Frequency: 25 Hz, 50% Duty Ratio (20ms ON and 20ms OFF)
Isolation Voltage: 2500 VacCommunicationsModbus-RTU Protocol; RS-485 (Optional)ModBus Communications Protocol: MODBUS RTU (Industry Standard)
Type: 2 Wire Connection, Half-Duplex, Isolated
Baud Rate: 1200 to 38,400DisplayLCD Screen Display with White Back Light
Wide Environmental Temperature Endurance
Displays Load Percentage, 4 Quandrants Power and Load NatureAlarmsUp to 2 Parameters Set with Time Interval
Events Recorded with Time Stamps and Triggers Alarm DO Output
(35 Different Parameters Available)Operating RangeTemperature: -25°C to 70°C
Humidity: 5% to 95% Non-Condensing
Pollution Degree: 2Storage Range Temperature: -40°C to 85°C
Humidity: 5% to 95% Non-CondensingStandards ComplianceIEC 61010-1; UL 61010-1; cUL 61010-1Dimensions9.6cm x 9.6cm x 5.1cm (3.8" x 3.8" x 2.0")